Analysis and Treatment of Oil Level Abnormity Caused by Defects in Main Transformers
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The possible causes of the oil level abnormity were analyzed for the main transformer oil level abnormal defects,combined with the actual oil level,showed oil level and temperature-oil level curve.The length of pointer-type oil level swing-rod was calculated.The capacity of oil conservator was calculated and analyzed,and results show that it should be at least 10% of the body oil volume of main transformers.Defects and errors of existing main transformers were pointed out,and treatment measures and operational maintenance suggestions were put forward,which provides a reference for the main transformer acceptance and maintenance work.

    Reference
    Related
    Cited by
Get Citation

LUO Heng, SHI Qiuyun, HUANG Fen, WU Xi. Analysis and Treatment of Oil Level Abnormity Caused by Defects in Main Transformers[J]. Electric Power Engineering Technology,2017,36(3):105-109.