MMC子模块故障后线电压恢复容错控制策略
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM76

基金项目:

国家重点研发计划资助项目(2018YFB0904700)


Fault-tolerant control strategy of line voltage recovery after MMC sub-modules fault
Author:
Affiliation:

Fund Project:

National Key R&D Program Funded Projects(Grant No. 2018YFB0904700);This study is supported by the State Key Laboratory of Advanced Power Transmission Technology(Grant No. Geiri-skl-2020-011)

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    模块化多电平换流器(MMC)桥臂无冗余子模块(SM)时,SM故障将导致故障相电压输出能力降低,进而导致MMC输出线电压不平衡。为恢复故障后无冗余MMC输出线电压特性,提高非故障桥臂SM利用率,文中基于中性点转移(NT)与直流分量注入(DCCI)控制,提出应用于无冗余MMC的SM故障容错控制策略。该容错策略通过NT控制,调整三相电压相角,确保输出线电压平衡。此外,文中提出三段式最优DCCI幅值计算方法。与现有方法相比,最优幅值DCCI能进一步提升非故障桥臂SM利用率,提高输出线电压幅值。基于PSCAD/EMTDC平台搭建三相MMC仿真模型,仿真结果验证了所提容错控制策略的有效性。

    Abstract:

    When the modular multilevel converter (MMC) arms do not have redundant sub-modules, the fault of the sub-modules decreases the output voltage capability of the faulty phase, which leads to the unbalanced output line voltage of the MMC. In order to restore the post-fault output line voltage characteristics of the no-redundant MMC and improve the utilization rate of the non-faulty arm's sub-modules, a sub-module fault-tolerant control strategy which is suitable for non-redundant MMC is proposed based on neutral point transfer (NT) and direct current component injection (DCCI) control. The fault-tolerant strategy adjusts the phase angle of the three-phase voltage through NT control for ensuring the balance of the output line voltage. In addition, a three-stage optimal DCCI amplitude calculation method is proposed. Compared with the existing methods, the optimal amplitude DCCI further improves the utilization rate of the non-faulty arm's sub-modules and increases the output line voltage amplitude. A three-phase MMC simulation model based on the PSCAD/EMTDC platform is built, and the effectiveness of the proposed no-redundant fault-tolerant control strategy is verified through the simulation results.

    参考文献
    相似文献
    引证文献
引用本文

夏长江,韩民晓,耿治,寇龙泽. MMC子模块故障后线电压恢复容错控制策略[J].电力工程技术,2021,40(4):2-9

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2021-02-04
  • 最后修改日期:2021-04-21
  • 录用日期:2021-06-21
  • 在线发布日期: 2021-08-11
  • 出版日期: 2021-07-28