谐波附加控制抑制直流输电连续换相失败研究
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM711

基金项目:

江苏省政策引导类计划(国际科技合作)资助项目“区域综合能源建模仿真与运行控制技术研究”(BZ2019057)


Suppressing HVDC continuous commutation failure by additional harmonic control
Author:
Affiliation:

Fund Project:

National Natural Science Foundation of China (51607092); Jiangsu province graduate research innovation project (KYCX18_1227)

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    换相失败是高压直流输电(HVDC)最为常见的故障之一,而我国特高压直流在控保系统内设置了连续换相失败启动直流主动闭锁的逻辑,连续换相失败及其可能造成的直流闭锁对电网的安全稳定运行造成了一定威胁。国内外关于抑制连续换相失败的研究已经取得部分研究成果,但就谐波对HVDC连续换相失败的影响研究方面还有待进一步深入。文中从HVDC换相过程出发,通过换相电压-时间面积分析法,推导出直流输电附加控制回路的各次谐波控制参数,并考虑低压限流控制对直流输电换相失败恢复过程的影响,提出一种谐波附加控制抑制直流输电连续换相失败的方法。最后,基于CIGRE HVDC标准测试模型,利用PSCAD/EMTDC对所提控制方法有效性进行了仿真验证。

    Abstract:

    The commutation failure is one of the most common faults in high voltage direct current transmission (HVDC) systems. In China, the control and protection system of ultra-high voltage direct current is provided with the logic of starting active DC blocking to avoid negative influence of continuous commutation failure. However, the possibility of DC blocking which is caused by the continuous commutation failure poses a certain threat to the safety and stability of operation in the power grid. The suppressing HVDC continuous commutation failure has received more attention by researchers around the world. However, the influence of harmonic on the HVDC continuous commutation failure has not been reported thoroughly yet. The method of commutation voltage-time area is applied to analyze commutation process for HVDC transmission, after which harmonic control parameters of additional control loop are obtained. In the recovery process, the influence of commutation failure on voltage dependent current order limiter is taken into account, and a method for reducing failure rate of HVDC continuous commutation with additional harmonic control is proposed. Finally, based on the CIGRE HVDC standard test system, the effectiveness of the proposed control method is verified by PSCAD/EMTDC.

    参考文献
    相似文献
    引证文献
引用本文

陈佳浩,王琦,朱鑫要,李宁.谐波附加控制抑制直流输电连续换相失败研究[J].电力工程技术,2021,40(2):86-92

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2020-10-09
  • 最后修改日期:2020-11-13
  • 录用日期:2020-06-01
  • 在线发布日期: 2021-04-02
  • 出版日期: 2021-03-28