    摘要:

    准确的故障测距是输电线路故障后快速恢复供电的重要前提。一般来说,线路上发生单相接地故障时,因过渡电阻的影响,导致计算阻抗无法正确反映保护安装处至故障点的线路阻抗值,必须借助双端测距才可获得精确测距值。文中在分析附加阻抗来源的基础上,提出在特殊的工况下,双端测距失效,基于三角形计算的单端测距可精确测距,并且此方法可以推广至架空线、地缆混合参数的输电线路故障。经过仿真数据以及现场数据验证,该方法具有较高的精度。

    Abstract:

    Precise fault location is an important precondition of quick power supply restoration after transmission line fault occurs.In generally,concerning one-phase to ground fault,it is the transient resistance that causes that the impedance from where the relay is installed to where the fault occurs is caculated incorrectly.On such scenario,a double-ended fault location algorithm is preferred in order to acquire rather precise fault location result.Based on analyzing the source of additive impedance,this essay presents that under some special working conditions whereas double-ended fault location becomes invalid,single-ended fault calculation based on solving triangle calculation gives precise results.And this method can also be applied to hybrid parameter transmission lines which have both overhead lines and cables.The simulation and field data verified that the method has high precision.